In within a rated wall assembly as long as the sum total area of openings wall cutouts for those boxes does not exceed 100 square inches for any 100 sq.
Cut in boxes in fire rated walls.
At that point put on the fire pad then have the wall closed up.
All boxes must also have more than 24 inches of horizontal spacing between outlets on either side of the fire rated wall.
Wall boxes suitable for epic series module 2.
Outlet and switch boxes on opposite sides of a wall or partition within the same stud cavity shall be separated by a horizontal distance of not less than 3 in.
These materials are found under cliv in the fire resistance directory published by ul.
Fire rated one and two hours 1.
Ceiling boxes and single gang outlet switch boxes may be used in a 2 hour or less fire rated floor ceiling assembly.
Generally the spacing between boxes cannot be less than 24 inches but closer spacing is permitted where wall opening protective materials are installed according to the requirements of their classification.
If it s a fire rated existing wall you will have to cut it open to mount your box to the framing and then have it patched.
Use the actual wall box as a cut out template whilst referring to the table above for recommended cut out dimensions 3.
This means that on 24 oc studs outlets must be placed at least one stud cavity away both sides of wall.
That s about as untrue as can be.
Used in both 2 and 1 hour fire rated wall assemblies.
The area of openings for boxes shall not aggregate more than 100 sq in.
There are several compliant fire rated boxes that can be secured to the stud that don t require you to cut anything open.
If required remove knockout from wall box for suitable cable entry 5.
Clearance between boxes and cut outs in wall shall not exceed 1 8 in.
Boxes are suitable for installation in staggered stud wall configuration.
See carlon s ner 140 report or the ul fire resistance directory which describes in detail the use of zip boxes in these assemblies.